
Gas Burner Assembly
Upper Burner System-Operational Sequence
Gas Burner Assembly
Upper Burner System-Operational Sequence
¾With ignition present on the upper burners, the upper ignition
module must sense that flame is present.
¾This is accomplished through flame rectification.
¾The upper ignition module applies a voltage between the flame
sensor and ground (the burner). With a flame present between
the flame sensor and ground, the flame completes the circuit’s
path. Rectification occurs through the flame and a small DC
current can be sensed.
¾This measurement can be taken from the upper ignition module
and anything above 0.7 μA proves that flame is present.
Kommentare zu diesen Handbüchern